Frame Leakage Protection of Transformer:
Frame Leakage Protection of Transformer – The transformer is mounted insulated from the ground, as illustrated in Fig. 12.14. The transformer tank is connected to earth through a CT to which an instantaneous earth fault relay is connected.
In the case of an earth fault in the transformer (breakdown of insulation in any winding of the transformer), there is a flow of current to the earth over this connection causing the relay to operate.
Such an arrangement is usually provided where banked transformers are provided with a single overall differential protection and it is difficult to find as to which transformer is faulty.